62
c) Input/Output Jumper Configuration
NOTE: Your TIO device input / output jumpers were configured at the
factory according to your order. There is no need to change the input
/ output jumper’s configuration unless different input is being used.
Before applying power and process signals make sure the input /
output jumpers are installed in the correct position (See Table 6.4).
,
TABLE 6.4 J2 INPUT / OUTPUT JUMPER CONFIGURATION OPTIONS FOR GFC SERIES
FLOW CONTROLLERS
TIO PV TYPE J2 JUMPER CONFIGURATION
GFC
CABLE KIT
NOTE
OUTPUT INPUT J2A J2B J2C J2D J2E J2F
0-5Vdc 0-5Vdc 2 - 3 5 - 6 8 - 9 10-11 14-15 17-18
KIT-TC-
XXXXX-XX
Supported by
all GFC Kits,
except
KIT-TC
0-5Vdc
4-20
mA
2 - 3 5 - 6 8 - 9 10-11 13-14 16-17
N/A (user
custom
cable
assembly
only)
Not supported
by GFC Cable
Kits
4 – 20
mA
0-5Vdc 1 - 2 4 - 5 7 - 8 10-11 14-15 17-18
N/A (user
custom
cable
assembly
only)
Not supported
by GFC Cable
Kits
4 – 20
mA
4 – 20
mA
1 - 2 4 - 5 7 - 8 10-11 13-14 16-17
N/A (user
custom
cable
assembly
only)
Not supported
by GFC Cable
Kits
0 - 10
Vdc
0 - 10
Vdc
2 - 3 5 - 6 8 - 9 11-12 14-15 17-18
NOT
SUPPORTED
BY GFC
Special Order
option! (PCB
hardware
must be
changed)
Vue de la page 64