COMMAND
NAME
DESCRIPTION
NO.
COMMAND SYNTAX
COMMAND ARGUMENT 1 ARGUMENT 2 ARGUMENT 3 ARGUMENT 4 RESPONSE
Totalizers Sets and controls action of
the flow Totalizers.
NOTE: Start Totalizer at
Flow value must be entered
for in %FS (0.0 – 100.0).
Limit volume must be
entered in currently selected
EU. If Totalizer hit limit
event is not required, set
“Limit Volume” value (argu-
ment 4) to zero. Totalizer#1
can be configured to Count
Up only (argument M is not
supported). Totalizer#2 can
be configured to Count Up
or Count Down mode.
When configured to Count
Down mode, limit volume
must be more than zero.
Totalizer#1 reading is stored
in EEPROM (non-volatile)
memory. Power cycle will
not affect Totalizer#1 read-
ing.Totalizer#2 reading is
backed up in EEPROM with
6 minutes interval. Power
cycle may affect Totalizer#2
reading. Totalizer#1 cannot
be reset if ResetLock (EE
index 70) value set to 1.
11
T
1 (Totalizer #1)
2 (Totalizer #2)
Z
(Reset to zero)
T1Z or T2Z
C
Start flow and Event
Condition
<value>
(start Totalizer at flow)
%FS [0.0 – 100.0]
<value>
(Limit volume In current
volume based EU)
T1C:2.5, 0.0
or T2C:2.0,20580.5
P
Power On Delay
<value>
(0-3600 sec.)
T1P:10 or T2P:20
D (disable Totalizer)* T1:D or T2:D
E (enable Totalizer) T1:E or T2:E
R (read current Totalizer
volume)
T1R:<value> or
T2R:<value> (in current EU)
S
(read current
settings status)
T1S:Mode,Direction,Start
Flow,LimitVolume,
PowOnDelay,AutoResetMode,
AutoResetDelay Example:
T1S:E,0,0.5, 2045.2,10,0,5
A
Set Auto Reset/Reload
mode
<value> [0-1]
0 – Disable
1 – Enable
T1A:0 - disabled
Or T2A:1 - enabled
I
Set Auto Reset/Reload
Interval delay
<value>
[0-3600 sec.]
T1I:2 Or T2I:0
B
Restore Totalizer#1
value from EE backup
T1B
Not supported by Totalizer #2.
M
Totalizer#2 counting
direction configuration
<value> [0-1]
0- Count Up
1-Count Down
T1M:0
Not supported by Totalizer #1.