Aalborg TIO Totalizer I/O Flow Monitor/Controller Manuel d'utilisateur Page 90

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 98
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 89
87
COMMAND
NAME
DESCRIPTION
NO.
COMMAND SYNTAX
COMMAND
ARGUMENT 1 ARGUMENT 2 ARGUMENT 3 ARGUMENT 4
RESPONSE
Signal
Conditioner
Settings
Sets/Reads Signal Conditioner
Parameters
Argument1 = F:
Display/Change NR Filter
Parameters:
NRF Sample Number [1-32]
NRF Time Limit [0-199]
NRF Error Limit [0.0-10.0%]
16
SC
M
Read/Change Device
Signal Conditioner
Mode
N – No Conditioning
F – NRF Filter
A – Running Average
<New Mode>
[N, F, A]
SCM:<value>
Example:
SCM:F
No Argument
(Returns Current
Mode)
SCM:<value>
Example:
SCM:F
D
Flow Running
Average Damping
[0-500 ms]
0 - Disabled
<new value>
in ms [0-500]
SCD:<value>
Example: SCD:50
No Argument
(Returns Current set.)
PWD:<value>
Example: SCD:50
F
NR Filter Settings:
NRF Sample Numb.
NRF Time Limit
NRF Error Limit
<new value>
Sample#
[1-32]
<new val.>
Time Limit
[0-199]
<new val.>
Error Limit
[0.0-10%]
Example:
PWF:4,8,0.0
No Argument
(Returns Current
set.)
Example:
PWF:4,8,0.0
L
Device Flow
Linearizer
E- Enable
D- Disable
<New Value>
E or D
SCL:<value>
Example: SCL:E
No Argument
(Ret. Current
settings)
SCL:<value>
Example: SCL:E
Vue de la page 89