Aalborg TIO Totalizer I/O Flow Monitor/Controller Manuel d'utilisateur Page 76

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 98
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 75
73
INDEX NAME DATA TYPE NOTES
71
Total1_Volume_BkUp
float
Totalizer#1 backup volume in %s (saved every 6
minutes)
72
Total1_AutoReset
uint
Reset Total. Volume value when Totalizer value
equals Limit volume 0 - No, 1 - Yes
73
Total1_AtoResetDelay
uint
Delay in seconds before AutoReset will reset
Totalizer#1 volume reading to zero [0-3600]
74
Total1_Reserved
uint
Totalizer#1 reserved
75
Total2_Mode
uint
Totalizer#2 mode: (0-Disabled, 1-Enabled)
76
Total2_Config
uint
Totalizer#2 configuration (0-Count Up, 1-Count Down)
77
Total2_FlowStart
float
Start tot. at flow [0-1.0 fraction notation %F.S.]
78
Total2_VolStop
float
Limit volume in %s, 0 = disable
79
Total2_PowOnDelay
uint
Totalizer#2 power on delay in second [0-3600]
80
Total2_Volume_BkUp
float
Totalizer#2 backup volume in %s (saved every 6
minutes)
81
Total2_ReloadVolStop
uint
Reload VolStop value when Totalizer reading counts
down to zero 0 - No, 1 - Yes
82
Total2_ReloadDelay
uint
Delay in seconds before Reload VolStop value when
Totalizer reading counts down to zero [0-3600]
83
Total2_10SecBackUp
uint
Enable or Disable every 10 seconds EEPROM backup
(reserved for future version release)
84
Total2_Reserved
uint
Totalizer#2 reserved
85
Flow_Pulse_Mode
uint
Flow Pulse Output Mode (0=Dis'd, 1=En'd)
86
PulseFlowStart
float
Start pulse output at flow [0-1.0 fraction notation %F.S.]
87
Units_Per_Pulse
float
Units per pulse scaling
88
Active_Low_Time
uint
Number of ms output will be activated when pulse is
developed
89
Flow_Pulse_Reserved
uint
Pulse Output Reserved
90
FlowCondMode
uint
0 - No conditioning, 1 - NRF, 2 - Running Average
91
Flow_NRF_NSample
uint
Flow NRF Number of Samples [1 - 32]
92
Flow_NRF_ErrLimit
float
Flow NRF Error Value [0.05 10.0] %F.S. (FN)
93
Flow_NRF_TimeLimit
uint
Flow NRF Time Interval [0-199], 0 - disabled
94
Flow_Damping
uint
Reading Damping 0-500 ms
95
Flow_Window
uint
Flow running average window [0-32] 0-disable
96
FlowLinearizer
uint
Flow Linearizer: On (1), Off (0)
97
Flow_SC_Reserved
uint
Flow Signal Conditioner reserved
98
FlowTbl[0].FlowPFSIn
float
Flow Linearizer Index 0 PFS In (must be 0.0)
99
FlowTbl[0]. FlowPFSOut
float
Flow Linearizer Index 0 PFS Out (must be 0.0)
100
FlowTbl[1]. FlowPFSIn
float
Flow Linearizer Index 1 PFS In [0.0 – 1.0]
101
FlowTbl[1]. FlowPFSOut
float
Flow Linearizer Index 1 PFS Out [0.0 – 1.0]
102
FlowTbl[2]. FlowPFSIn
float
Flow Linearizer Index 2 PFS In [0.0 – 1.0]
103
FlowTbl[2]. FlowPFSOut
float
Flow Linearizer Index 2 PFS Out [0.0 – 1.0]
104
FlowTbl[3]. FlowPFSIn
float
Flow Linearizer Index 3 PFS In [0.0 – 1.0]