Aalborg Vortex Insertion Manuel d'utilisateur Page 19

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 123
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 18
14
4.5.4 Programmable optically isolated Flow Pulse
Output Signal Connections
Terminal TB4 (pins 2 and 1):
Terminal TB4 Pin 2 --------------- Plus (+) (passive)
Terminal TB4 Pin 1 --------------- Plus (-) (passive)
WARNING: Optically isolated Flow Pulse output require application of
external DC voltage across terminals. Do not exceed maximum allowed
limits for voltage and current provided below:
2 V UCE 60 V
0.2 mA ICE 50 mA
WARNING: Optically isolated outputs require application of external DC
voltage across terminals. Do not exceed maximum allowed limits for
voltage and current provided below:
2 V UCE 40 V
0.2 mA ICE 150 mA